doc:appunti:hardware:ups_apc_nut
Table of Contents
Using an APC UPS with the Nut software
Configuration
Configuration files into /etc/nut/ directory:
- nut.conf
- ups.conf
- upsd.conf
- upsd.users
- upsmon.conf
/etc/nut/nut.conf
MODE=standalone
/etc/nut/ups.conf
[apc-bx2200]
driver = usbhid-ups
port = auto
#serial = "9B2611A02967"
desc = "APC Back-UPS BX2200MI"
ignorelb
pollonly
/etc/nut/upsd.conf
LISTEN 127.0.0.1 3493 LISTEN 192.168.0.46 3493
/etc/nut/
[admin]
password = MySecret1
actions = SET
instcmds = ALL
[monuser]
password = MySecret2
upsmon master
/etc/nut/upsmon.conf
MONITOR apc-bx2200@localhost 1 monuser MySecret2 master
Usage
List the UPS configured with nut:
upsc -l apc-bx2200
Display the status of the named UPS:
upsc apc-bx2200
Display the value of one variable only.
upsc apc-bx2200 ups.status upsc apc-bx2200 battery.charge upsc apc-bx2200 battery.runtime upsc apc-bx2200 ups.alarm upsc apc-bx2200 ups.load
Show the list of supported instant commands on that UPS.
upscmd -l apc-bx2200
Inizia un test rapido della batteria (richiede autenticazione):
upscmd apc-bx2200 test.battery.start.quick
upscmd apc-bx2200 beeper.mute upscmd apc-bx2200 beeper.disable upscmd apc-bx2200 beeper.enable
upsc apc-bx2200 ups.beeper.status
doc/appunti/hardware/ups_apc_nut.txt · Last modified: by niccolo