====== Using an APC UPS with the Nut software ====== ===== Configuration ===== Configuration files into **/etc/nut/** directory: * **nut.conf** * **ups.conf** * **upsd.conf** * **upsd.users** * **upsmon.conf** === /etc/nut/nut.conf === MODE=standalone === /etc/nut/ups.conf === [apc-bx2200] driver = usbhid-ups port = auto #serial = "9B2611A02967" desc = "APC Back-UPS BX2200MI" ignorelb pollonly === /etc/nut/upsd.conf === LISTEN 127.0.0.1 3493 LISTEN 192.168.0.46 3493 === /etc/nut/ === [admin] password = MySecret1 actions = SET instcmds = ALL [monuser] password = MySecret2 upsmon master === /etc/nut/upsmon.conf === MONITOR apc-bx2200@localhost 1 monuser MySecret2 master ===== Usage ===== List the UPS configured with nut: upsc -l apc-bx2200 Display the status of the named UPS: upsc apc-bx2200 Display the value of one variable only. upsc apc-bx2200 ups.status upsc apc-bx2200 battery.charge upsc apc-bx2200 battery.runtime upsc apc-bx2200 ups.alarm upsc apc-bx2200 ups.load Show the list of supported instant commands on that UPS. upscmd -l apc-bx2200 Inizia un test rapido della batteria (richiede autenticazione): upscmd apc-bx2200 test.battery.start.quick upscmd apc-bx2200 beeper.mute upscmd apc-bx2200 beeper.disable upscmd apc-bx2200 beeper.enable upsc apc-bx2200 ups.beeper.status